Parameters
Category Parameter Specification for 07KT97F1
General Module Type Universal, Multi-Range Analog Input Module
Compatible System ABB Freelance DCS, AC 700F/800F PLC, S800 I/O System
Form Factor S800 I/O Single-Width Module
Input Channels Number of Channels 8 channels (typical for this series).
Channel Isolation Individual channel-to-channel and channel-to-system isolation.
Analog Input Signals Configurable Types Voltage: 0-10V, ±10V
Current: 0-20mA, 4-20mA (with 2-wire transmitter supply)
Resistance: For RTDs (Pt100, Pt1000)
Thermocouple: Types J, K, T, E, N, R, S, B
Input Impedance Voltage: > 1 MΩ; Current: ≤ 250 Ω (internal shunt).
Transmitter Supply 24 V DC (per channel, for 2-wire transmitters).
Conversion & Performance Resolution 16-bit (or 15-bit + sign).
Conversion Time Per channel: Typically 20 - 50 ms for all 8 channels (scan rate).
Accuracy Typically ±0.1% of full scale (at 25°C, for voltage/current).
RTD: ±0.2°C; TC: ±1°C (typical).
Filtering Software-configurable digital filtering.
Diagnostics & Alarms Diagnostic Functions Wire break (open circuit), short circuit, underrange, overrange, module fault.
Status Indication LED per channel (green/red) for communication and fault status.
Electrical & Environmental Backplane Power +5V DC from the S800 power supply.
Field-Side Power 24V DC supplied to transmitters (if enabled).
Isolation Voltage Channel-to-Bus: Typically 500 V AC (1 min).
Operating Temperature 0°C to +60°C
Storage Temperature -40°C to +85°C
Relative Humidity 5% to 95%, non-condensing.
Communication Bus Interface Profibus DP or Foundation Fieldbus (depending on the connected fieldbus module, e.g., CI871).
Software Configuration Tool ABB Control Builder F (CBF) or Freelance Engineering.
The ABB 07KT97F1 is a universal, multi-range analog input module from ABB's Freelance distributed control system (DCS) and AC 700F/800F programmable logic controller (PLC) series. This module serves as the primary interface for connecting various analog field sensors (e.g., temperature via RTDs/thermocouples, pressure transmitters, level sensors) to the controller's I/O bus, enabling precise process monitoring and control.