Technical Data
Parameter Specification / Value
Application Standard IEC/EN 61643-11
Protection Type / Class Type 1 + Type 2 Combined (Class I + II)
Rated Voltage (Un) 400 V AC, 3P+N (50/60 Hz)
Maximum Continuous Operating Voltage (Uc) 420 V AC (Line-Line & Line-Neutral)
Impulse Discharge Current (Iimp) 10/350 µs 60 kA (per pole, L/N) - This is the critical Type 1 parameter.
Nominal Discharge Current (In) 8/20 µs 70 kA (per pole)
Maximum Discharge Current (Imax) 8/20 µs 100 kA (per pole)
Voltage Protection Level (Up) at In ≤ 2.5 kV (Line-Neutral)
Response Time < 100 ns
Short-Circuit Withstand Rating (SCCR) According to IEC 61643-11
Back-up Fuse Recommendation Required. Typically 160 A gL/gG or 200 A fuse per phase (MUST be verified with local regulations and the latest ABB datasheet).
Connection Cross-Section Main Terminals: 35 - 95 mm² (copper)
Earth Terminal: 50 - 95 mm² (copper)
Housing Material Thermoplastic (UL94 V-0)
Protection Degree (IP) IP20 (for indoor installation in an appropriate enclosure)
Operating Temperature Range -40 °C to +80 °C
Status Indication Visual (color flag: green=OK, red=fault)
Mounting DIN-rail mountable (35 mm) or direct panel mounting
Dimensions (H x W x D) Approx. 288 mm x 90 mm x 75 mm (Please confirm with official datasheet)
The ABB PSE370-600-70 is a Type 1+2 Combined Surge Protective Device (SPD) from ABB's PSE series. It is a three-phase, four-pole (3P+N) high-energy surge arrester designed for installation at the service entrance (main distribution board) of low-voltage AC power systems.