Technical Data
Parameter Specification / Value
Application Standard IEC/EN 61643-11
Protection Type / Class Type 1 + Type 2 Combined (Class I + II)
System & Rated Voltage 400 V AC, 3P+N (50/60 Hz)
Maximum Continuous Operating Voltage (Uc) 320 V AC (Line-Neutral) / 420 V AC (Line-Line)
Impulse Discharge Current (Iimp) 10/350 µs 60 kA (per pole)
Nominal Discharge Current (In) 8/20 µs 70 kA (per pole)
Maximum Discharge Current (Imax) 8/20 µs 100 kA (per pole)
Voltage Protection Level (Up) @ In ≤ 2.0 kV (Line-Neutral)
Response Time < 100 ns
Short-Circuit Withstand Rating According to IEC 61643-11
Back-up Fuse Recommendation Required. Typically 125 A or 160 A gL/gG (Consult local regulations and the official ABB installation guide).
Connection Cross-Section Line & Neutral: 16 - 70 mm² (copper)
Earth/PE: 25 - 70 mm² (copper)
Housing Material Thermoplastic (UL94 V-0)
Protection Degree (IP) IP20 (for mounting inside an enclosure)
Operating Temperature Range -40 °C to +80 °C
Status Indication Visual window with color flag (Green = OK, Red = Fault/End-of-Life)
Mounting DIN-rail mountable (35 mm)
Dimensions (H x W x D) Approx. 288 mm x 90 mm x 75 mm (Verify with latest datasheet)
Key Model Decode (PSE300-600-70) PSE: Series
300: Uc & Platform Code (320/420V)
600: Iimp = 60 kA
70: In = 70 kA
The ABB PSE300-600-70 is a Compact Combined Type 1+2 Surge Protective Device (SPD) from ABB's advanced PSE product line. It is engineered as a three-phase, four-pole (3P+N) high-energy surge arrester for integration into the Main Distribution Board (MDB) or service entrance of low-voltage AC power networks (TN-S, TT, TN-C-S systems).