Key Technical Parameters (English)
General & Protection
Product / Model: ABB XT3N250 TMD250/2500 FF 4P
Device Type: Molded Case Circuit Breaker (MCCB)
Series: SACE Tmax XT
Number of Poles: 4 (three phases + neutral)
Trip Unit Type: Thermal‑Magnetic (TMD)
Mounting Style: Fixed with front terminals
Current & Voltage Ratings
Rated Continuous Current (In): 250 A
Overload Trip Setting Range: Adjustable (typically a range ending at 250 A)
Instantaneous Short‑Circuit Setting: 2500 A
Rated Operational Voltage: Up to 690 V AC and 500 V DC
Rated Frequency: 50 Hz / 60 Hz
Rated Insulation Voltage (Ui): 800 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Breaking Capacities
Rated Ultimate Short‑Circuit Breaking Capacity (Icu) – AC:
~50 kA at 220–240 V AC
~36 kA at 380–415 V AC
~25 kA at 440–500 V AC
~5 kA at 690 V AC
Rated Service Short‑Circuit Breaking Capacity (Ics) – AC:
~50 kA at 220–240 V AC
~36 kA at 380–415 V AC
Lower values at higher voltages (e.g., ~18 kA at 440 V AC, ~3.75 kA at 690 V AC)
DC Breaking Capability:
~36 kA at 250 V DC (2 poles in series)
~50 kA at 500 V DC (3 poles in series)
Performance & Durability
Electrical Durability: ~8,000 operating cycles
Mechanical Durability: ~25,000 cycles
Power Loss per Pole at Rated Conditions: ~17.8 W
Terminal Connection: Bolt / front terminals with recommended tightening torque
Physical & Environmental
Dimensions: Approx. 140 mm × 150 mm × 70 mm (height × width × depth)
Weight: ~2 kg
Degree of Protection: Standard industrial MCCB housing (typically IP20 on terminals)
Operating Environment: Suitable for industrial distribution panels and switchboards
Applications
Protection of three‑phase power distribution circuits
Motor feeder and branch circuit protection
The ABB XT3N250 TMD250/2500 FF 4P is a four‑pole molded case circuit breaker (MCCB) from ABB’s Tmax XT series, designed for industrial and commercial power distribution protection. It provides combined thermal and magnetic protection to defend electrical circuits against overloads and short‑circuits. The four‑pole design (three phases plus neutral) with front terminals is suited for fixed installation in switchboards and distribution panels. Adjustable trip characteristics allow coordinated protection of three‑phase systems and neutral circuits.