Key Technical Parameters
General & Monitoring
Product / Model: ABB CM‑PVS.41S Three‑Phase Monitoring Relay
Part Number: 1SVR730794R3300
Function: Monitors three‑phase supply for overvoltage, undervoltage, phase failure, and phase sequence faults
Supply / Measuring Voltage: 300 V to 500 V AC between phases (L‑L)
Measuring Frequency: 50 Hz / 60 Hz
Output & Contacts
Output Type: 2 change‑over (SPDT) contacts
Contact Ratings: Up to 250 V AC at 4 A (typical control load)
Timing
Startup Delay: ~200 ms
Tripping Delay: Adjustable from instantaneous to 30 s
Connection & Installation
Mounting: DIN‑rail (standard TH35)
Terminal Type: Screw terminals with double‑chamber cage connection
Environmental
Operating Ambient Temperature: –25 °C to +60 °C
Storage Temperature: –40 °C to +85 °C
Degree of Protection: IP20 on terminals and housing
Physical
Width: ~22.5 mm
Height: ~85.6 mm
Depth: ~103.7 mm
Weight: ~0.139 kg
Typical Applications
Phase sequence and phase loss detection for motor protection systems
Over/undervoltage monitoring to protect equipment from abnormal supply conditions
Industrial control panels used in automation and machine control
Signal/alarm interfacing for PLCs or safety circuits upon fault detection
The ABB CM‑PVS.41S is a three‑phase monitoring relay designed to monitor the health of a three‑phase electrical supply. It continuously checks for overvoltage, undervoltage, phase loss, and incorrect phase sequence in three‑phase systems with line‑to‑line voltages within a specific range. When a fault condition is detected, the relay changes the state of its output contacts to signal alarms or to disconnect loads for protection. It is mounted on a DIN rail and typically used in industrial control panels, motor protection systems, and automation circuits to ensure correct and safe operation of three‑phase equipment.