Parameters
Category Parameter Specification for SK827005 (T5X 550 EH)
General Product Series SACE Tmax XT
Frame Type T5X
Rated Current (In) 550 A (Frame Rating)
Number of Poles 3 Poles
Tripping Unit Type Fixed Thermal-Magnetic Release (EH Type)
Rated Operational Values Rated Insulation Voltage (Ui) 1000 V AC
Rated Operational Voltage (Ue) 690 V AC
Rated Frequency 50/60 Hz
Breaking Capacities Ultimate Breaking Capacity (Icu) at 415V 50 kA (According to IEC 60947-2)
Service Breaking Capacity (Ics) at 415V 50 kA (100% of Icu for Tmax XT)
Tripping Characteristics (EH Fixed) Overload Protection (Ir) Fixed at 550 A (Non-adjustable). Trip characteristic per IEC 60947-2.
Short-Circuit Protection (Im) Fixed Magnetic Trip. Typically set at 10 x In (5500 A) or similar fixed multiple.
Mechanical & Electrical Electrical Durability 8,000 operations (at In)
Mechanical Durability 20,000 operations
Terminals Rated Torque Front/Rear: Typically 25 - 30 Nm for main terminals.
Cable/Busbar Connection Accepts busbars or cables with appropriate lugs. Max cable size typically up to 2x 240 mm² per pole.
Standards & Approvals Compliance Standards IEC/EN 60947-2, UL 489, CSA C22.2 No. 5
Certifications CE, cULus, CCC, etc.
Environmental Operating Temperature -25°C to +70°C (Ambient)
Storage Temperature -40°C to +80°C
Physical Data Approx. Dimensions (W x H x D) ~155 x 210 x 130 mm (3-pole, T5X)
Approx. Weight ~7.5 kg
The ABB SK827005 EH550 is a high-performance, molded case circuit breaker (MCCB) from ABB's well-established SACE Tmax XT series. This specific model, designated as T5X, is a 550 Ampere frame, three-pole thermal-magnetic circuit breaker designed for main circuit protection and switching in low-voltage electrical distribution systems. The "EH" in the code indicates specific tripping unit characteristics, typically a fixed thermal-magnetic release (non-adjustable).