Technical Parameters
Parameter Category Specification
Product Family / Type Self-Powered Three-Phase Current Monitoring Relay
Protection Functions • Phase Loss Detection
• Phase Sequence (Rotation) Monitoring
• Current Asymmetry (Unbalance) Protection
Standard Compliance IEC/EN 60947-5-1
Power Supply Self-powered from the secondary side of the connected current transformers (CTs).
Rated Input Current (In) 1 A AC (Secondary current of the CTs, defined by -600-).
Operating Current Range 0.1 A to 1.3 A AC per phase.
System Frequency 50 / 60 Hz.
Protection Settings
• Threshold Current (I<) Adjustable via rotary switch. Sets the minimum current level for phase presence detection. Typical range: 0.15 x In to 0.95 x In.
• Asymmetry Trip Level Adjustable via rotary switch. Sets the permissible current imbalance between phases as a percentage. Typical range: 20% to 70% asymmetry.
• Phase Sequence Fixed for one direction (e.g., L1-L2-L3). Trip on reversal is instantaneous.
• Response Time Fixed internal delay (typically < 0.5s) to avoid nuisance tripping on transient conditions.
Output Contact
• Type 1 Changeover (CO) contact (SPDT: 1 NO + 1 NC).
• Rated Operational Current (Ie) 6 A at 250 V AC (Utilization category AC-15).
Binary Input
• Reset / Start Input (A1, A2) 1 input. Requires a 24-48 V DC pulse (defined by suffix -11) to close the output relay after a fault condition is cleared or upon initial energization.
Visual Indication 2 LEDs:
- GREEN (On): Power OK, correct phase sequence, all phase currents above threshold.
- RED (Trip): Fault detected (Phase Loss, Sequence Error, or Asymmetry).
Connection Terminals Screw-clamp terminals for:
- 3 Current Inputs (From 1A secondary CTs, must be connected in Star/Wye).
- Output Contact (13-14 NO, 21-22 NC).
- Reset Input (A1, A2).
Electrical Isolation Reinforced insulation between current circuits, output contact, and reset input.
Operating Temperature -25°C to +55°C
Storage Temperature -40°C to +85°C
Mounting Standard 35mm DIN Rail (EN 60715).
Housing & Protection Self-extinguishing thermoplastic (PA 6.6), IP40 (front), IP20 (terminals).
Dimensions (W x H x D) Approx. 22.5 mm x 100 mm x 112 mm (1 module width = 22.5mm).
Weight Approx. 0.15 kg.
Certifications CE, cULus, RoHS.
The ABB PSR25-600-11 is a self-powered, three-phase current monitoring relay from the ABB PSR series. It is a compact, reliable device designed to protect three-phase electrical equipment, primarily motors, from damage caused by faults in the supply network, specifically phase loss (single-phasing), phase sequence reversal, and excessive current asymmetry (unbalance).