Technical Parameters
Parameter Category Specification
Product Family / Type Self-Powered 3-Phase Voltage Monitor with Motor Start Feature
Monitoring Functions 1. Phase Sequence (Rotation) Control
2. Phase Loss / Undervoltage Detection
3. Voltage Asymmetry (Unbalance) Monitoring
4. Voltage Dip Ride-Through during Motor Start
Standard Compliance IEC/EN 60947-5-1
Power Supply Self-powered from the monitored 3-phase line voltage (L1, L2, L3).
Rated Operational Voltage (Ue) 3 x 208...480 V AC, 50/60 Hz (Phase-to-Phase).
Current Input (for Start Logic) 1 A AC nominal (via external Current Transformers - CTs).
Parameter Settings & Ranges
• Running Voltage Threshold (U<) Adjustable via potentiometer. Sets the minimum permissible voltage during normal operation.
• Start Voltage Threshold Fixed internally or linked to Running Threshold. A less sensitive level active only during motor start.
• Voltage Asymmetry (ΔU) Adjustable via potentiometer. Sets the maximum allowed voltage difference between phases.
• Start Time Fixed internal timer defining the duration of the start monitoring mode (typically a few seconds).
Output Contact
• Type 1 Changeover (CO) contact (SPDT).
• Rated Operational Current (Ie) 6 A at 250 V AC (AC-15 category).
Binary Input
• Reset / Start Input 1 input (Terminals A1, A2). Requires a 24-48 V DC pulse (suffix -11) to close the output contact after a fault or initial power-up.
Visual Indication 2 LEDs:
- GREEN (On): Supply healthy, correct sequence, parameters within limits.
- RED (Trip): Fault condition (Loss, Unbalance, or Sequence Error).
Electrical Connections Screw-clamp terminals for:
- 3 Phase Voltages (L1, L2, L3).
- 3 Current Inputs (From 1A secondary CTs, star-connected).
- Output Contact (13-14 NO, 21-22 NC).
- Reset Input (A1, A2).
Isolation Reinforced insulation between all circuits: mains voltage, CT inputs, output contact, reset input.
Operating Temperature -25°C to +55°C
Storage Temperature -40°C to +85°C
Mounting Standard 35mm DIN Rail.
Housing & Protection Thermoplastic housing, IP40 (front), IP20 (terminal area).
Dimensions (W x H x D) Approx. 45 mm x 100 mm x 112 mm (2 module width).
Weight Approx. 0.2 kg.
Certifications CE, cULus, RoHS.
The ABB PSR30-600-11 is a self-powered, three-phase voltage monitoring relay with integrated motor start current logic. It is a member of the versatile ABB PSR series, designed to protect three-phase equipment—especially motors—from damage caused by incorrect or unstable power supply conditions.