Industrial Controller
All product are in stock,guaranteed delivery within 3-7 days.
Infinite Innovation, the Future of Industrial Control Systems
Infinite Innovation, the Future of Industrial Control Systems
PRODUCT POSITION:HOMEPRODUCT—D100A MA
D100A MA
The Schneider Electric D100A mA refers to a Residual Current Device (RCD/RCCB) with 100mA sensitivity from the Acti9 iDPN or iID series, specifically designed for earth leakage protection in electrical installations. This device provides protection against electric shock and fire risks caused by earth fault currents.
DESCRIBE
Specifications Parameter Specification Product Range Acti9 (iDPN / iID series) Device Type Residual Current Device (RCD) / Residual Current Circuit Breaker (RCCB) Rated Current (In) 100 Amperes (A) Rated Residual Operating Current (IΔn) 100 mA (0.1A) Residual Current Types Type AC (AC currents only) Type A (AC + pulsating DC) Type F (Frequency converter loads) Type B (AC, pulsating DC, smooth DC) Pole Configurations 2P (1P+N) or 4P (3P+N) - must be specified Rated Operational Voltage (Ue) 230V AC (2P) / 400V AC (4P) Rated Frequency 50/60 Hz Tripping Time ≤0.3s at IΔn (100mA) ≤0.15s at 2×IΔn (200mA) ≤0.04s at 5×IΔn (500mA) Non-tripping Current ≥0.5 × IΔn (≥50mA) Short-circuit Withstand Capacity Typically 6kA or 10kA (with upstream protection) Mechanical Durability 20,000 operations Electrical Durability 4,000 operations at IΔn Mounting DIN Rail (35mm) Width (Modular Size) 2 modules (36mm) for 2P 4 modules (72mm) for 4P Terminal Capacity Up to 35mm² copper conductor Ambient Temperature -25°C to +60°C Storage Temperature -40°C to +85°C Standards Compliance IEC/EN 61008-1, IEC/EN 61009-1
SERVICE HOTLINE Grace +86 13600179521
Mail jilineasyyi@outlook.com ADDRESS Unit 12, 20th Floor, Good View Commercial Centre, 2-16 Garden Street, Mong Kok, Hong Kong
Q Q: info@hongkongeasy.com
吉林易择科技技术发展有限公司 吉ICP备2024020526号-1
js