The Schneider Electric C100A 30mA refers to a Residual Current Circuit Breaker with Overcurrent Protection (RCBO) from the Acti9 series, combining the functions of a 100A Miniature Circuit Breaker (MCB) and a 30mA Residual Current Device (RCD) in one integrated device.
Specifications
Parameter Specification
Product Range Acti9 (iC60, iC65 or iID series depending on specific model)
Device Type Residual Current Circuit Breaker with Overcurrent Protection (RCBO)
Rated Current (In) 100 Amperes (A)
Rated Residual Operating Current (IΔn) 30 mA (0.03A)
Tripping Characteristic C Curve (5-10 × In magnetic trip)
Residual Current Type Type A (AC + pulsating DC) - most common
Type AC also available
Pole Configuration 2P (1P+N) or 4P (3P+N) - must be specified
Rated Operational Voltage (Ue) 230V AC (2P) / 400V AC (4P)
Breaking Capacity (Icn) 6kA, 10kA, or 15kA depending on model
Tripping Time ≤0.3s at IΔn (30mA)
≤0.15s at 2×IΔn (60mA)
≤0.04s at 5×IΔn (150mA)
Non-tripping Current ≥0.5 × IΔn (≥15mA)
Overcurrent Protection - Thermal: 1.13×In (113A) no trip in 1h
- Magnetic: 5-10×In (500-1000A)
Mechanical Durability 10,000 operations
Electrical Durability 4,000 operations at rated current
Mounting DIN Rail (35mm)
Width (Modular Size) 2 modules (36mm) for 2P
4 modules (72mm) for 4P
Terminal Capacity 25-50mm² copper conductor
Ambient Temperature -25°C to +60°C
Storage Temperature -40°C to +85°C
Standards Compliance IEC/EN 61009-1