CHIP ELECTRONIC COMPONENTS
Infinite innovation, the future of chip systems
PRODUCT POSITION:HOMEPRODUCT—9200-06101n
9200-06101n
Key Features: Dual-function monitoring: Simultaneously measures shaft vibration (0-500 µm) and axial position (±1mm to ±5mm) Advanced sensor compatibility: Works with industry-standard 8mm/11mm eddy current probes Flexible outputs: Offers 4-20mA, ±10V analog signals and Modbus RTU communication Multi-level protection: Configurable Warning/Danger alarms with relay outputs Wide operating range: Functions in extreme temperatures (-30°C to +70°C) with IP66/IP67 protection Typical Applications: Continuous monitoring of turbines, compressors and large rotating equipment Machinery protection in power generation and oil & gas industries Predictive maintenance programs for critical assets
DESCRIBE
General Specifications
Model: EPRO 9200-06101n (part of the 9200 series)

Primary Function: Vibration and axial position monitoring for turbomachinery

Compliance: Meets ISO 7919 (shaft vibration) and API 670 (machinery protection standards)

Input Signals
Sensor Compatibility:

Eddy Current Probes (8 mm or 11 mm, for shaft vibration & position)

Velocity Sensors (optional, for casing vibration)

Channels: Typically 2 vibration + 1 position (varies by configuration)

Measurement Ranges:

Shaft Vibration (Displacement): 0–500 µm (peak-to-peak, adjustable)

Axial Position (Thrust): ±1 mm to ±5 mm (selectable range)

Velocity (Casing Vibration): 0–50 mm/s RMS (if supported)

Signal Processing
Frequency Response:

Vibration: 0.5 Hz – 10 kHz (for shaft monitoring)

Position (DC Gap Voltage): 0–10 kHz (for slow-roll compensation)

Filtering:

High-pass/low-pass filters for noise reduction

Integration/differentiation for velocity/acceleration outputs

Outputs & Communication
Analog Outputs:

4–20 mA (isolated, proportional to vibration/position)

±10 V DC (for direct analysis or recording)

Relay Outputs:

3–4 relays (Warning/Danger for vibration & position)

Contact Rating: 250 VAC, 5 A (resistive load)

Digital Communication:

RS-232/RS-485 (Modbus RTU)

Optional PROFIBUS-DP or Ethernet (model-dependent)

Alarm & Protection
Adjustable Setpoints:

Independent Warning/Danger levels for vibration & position

Dynamic Alarm Delay: 0.1–10 sec (prevents false triggers during startups)

Power Supply
Voltage: 24 VDC (±10%) or 100–240 VAC, 50/60 Hz

Power Consumption: ≤6 W

Environmental & Mechanical
Operating Temperature: -30°C to +70°C

Enclosure Rating: IP66/IP67 (dust/waterproof)

Mounting: DIN rail or panel-mounted

Certifications
CE, ATEX/IECEx (for hazardous areas, if applicable)

ISO 9001 (quality management)

Typical Applications
Gas/Steam Turbines, Compressors, Generators

Shaft vibration & thrust position monitoring

Integration with DCS/PLC systems (e.g., Siemens, Allen-Bradley