Parameter Specification
Standards Compliance IEC/EN 60947-1 & 60947-2, UL 489, CCC, CE.
Rated Operational Current (Ie) 100 A (Set via installed rating plug).
Frame Current (Inm) 315 A
Poles 4 Poles (3P + N)
Rated Insulation Voltage (Ui) 1000 V
Rated Operational Voltage (Ue) Up to 690 V AC
Ultimate Breaking Capacity (Icu) 50 kA @ 415V AC (Category E)
Trip Unit Type Electronic (PR221DS/PR222DS type)
Key Protection Functions • L - Overload Protection: Adjustable current setting (Ir: 0.4 to 1 x In) and time delay (tr).
• S - Selective Short-Circuit Protection: Adjustable current threshold (Isd: 1.5 to 10 x Ir) and adjustable time delay (tsd) for coordination.
• I - Instantaneous Protection: Adjustable magnetic threshold (Ii: 2 to 14 x In).
Auxiliary Functions • Communication Ready: Built-in port for optional communication modules (e.g., ABB COM-xx modules for Modbus, Profibus DP).
• Measurement: Capable of monitoring current, power, energy, etc., visible via communication.
Mounting Fixed Mounting Version (can be used with fixed or plug-in base/adaptor).
Typical Applications
Main and sub-distribution switchboards
Industrial plant power distribution
Protection of feeders, motors, and capacitor banks
Integration into Building Management Systems (BMS) and SCADA via communication.
The ABB OTM315E4C10D380C is a fully featured Molded Case Circuit Breaker (MCCB) from ABB's advanced OTM series (previously known as the Tmax XT series). It is a high-performance, current-limiting air circuit breaker designed for reliable protection and control in industrial and commercial low-voltage electrical installations