Technical Parameters
Parameter Description / Value
Product Series / Family Tmax XT (incorporating T5 Series)
Breaker Type Molded Case Circuit Breaker (MCCB), Fixed Version
Frame Size 630A
Rated Current (In) 630 A (This is the maximum breaker rating. The actual fixed trip setting is tied to this frame size.)
Rated Operational Voltage (Ue) Up to 690 V AC
Poles 3 Poles (3P) - Standard configuration for the "A" version.
Breaking Capacity Category Standard (S) or High (H). Crucially, the code "T5-630A" alone does not specify this. It must be further defined (e.g., T5S630A or T5H630A).
Typical Ultimate Breaking Capacity (Icu) Must be specified with breaking capacity letter:
• For T5S630A: ~50 kA @ 415V AC (Standard).
• For T5H630A: ~70 kA @ 415V AC (High).
(Always verify with official data.)
Typical Service Breaking Capacity (Ics) Varies by category (e.g., 50% or 75% of Icu).
Trip Unit Type Fixed Thermal-Magnetic (A).
Protection Functions Thermal (L) - Inverse-time overload.
Magnetic (I) - Instantaneous short-circuit.
Standard IEC 60947-2
Electrical Durability Typically 6,000 - 8,000 operations at rated current.
Common Accessories Auxiliary contacts (OF/SD), shunt trip (MN), undervoltage release (MX), rotary handle (FHH), padlock attachments.
The ABB T5-630A is a Thermal-Magnetic Molded Case Circuit Breaker (MCCB) from ABB's Tmax XT series (incorporating the legacy T5 series). It is a three-pole, fixed-trip circuit breaker designed for reliable feeder and branch protection in a wide range of low-voltage applications, including industrial panels, commercial distribution boards, and machine main switches.