Technical Parameters
Parameter Description / Value
Product Series Emax (E1/E2 Generation)
Breaker Type Air Circuit Breaker (ACB), Draw-Out Version (WHR)
Frame Size E2N (1600A Frame)
Rated Current (Ir) 1600 A (Fixed setting)
Rated Operational Voltage (Ue) Up to 690 V AC
Breaking Capacity Category Normal (N)
Ultimate Breaking Capacity (Icu) Typically 50 kA @ 415V AC (Example for E2N frame). Must be verified from catalogue.
Service Breaking Capacity (Ics) Typically 50 kA @ 415V AC (Ics = Icu for Category N).
Trip Unit PR121/P - Electronic
Protection Functions L (Overload), S (Short-time delay), I (Instantaneous).
G (Ground Fault): NOT PRESENT/ACTIVE (NST).
Racking Mechanism Screw-type or push-pull type crank for moving between CONNECTED, TEST, and DISCONNECTED positions.
Control Voltage Required for spring charging motor and trip unit (e.g., 110-240V AC/DC).
Standards IEC 60947-2
The ABB E2N1600 R1600 PR121/P-LSI WHR3P NST is a draw-out type, low-voltage Air Circuit Breaker (ACB) from the original Emax (E1/E2) series. It is designed for main distribution in industrial plants, data centers, and large commercial facilities, offering selective protection and the major advantage of easy maintenance and isolation via its draw-out design.