Technical Parameters
Parameter Description / Value
Product Designation Electronic Trip Unit - PR222MP
Compatible Breaker Series ABB Tmax XT MCCBs (Frames: T4, T5, T6, T7)
Trip Unit Power Supply Self-powered from line current sensors for basic protection. Requires external 24V DC auxiliary supply for full functionality (display, communication, logging, protection at very low loads).
Protection Functions (Adjustable) L (Overload): Ir (0.4-1 x In), tr (delay).
S (Short-time): Isd (1.5-15 x Ir), tsd (delay).
I (Instantaneous): Ii (2-15 x In).
G (Ground Fault): Ig (0.2-0.8 x In, or fixed mA), tg (delay).
Measurement Accuracy Class 1 (per IEC 61557-12) for current and voltage.
Measured Electrical Parameters Current: Ia, Ib, Ic, In
Voltage: Vab, Vbc, Vca (via optional VT module)
Power: P (kW), Q (kvar), S (kVA)
Energy: Ep (kWh), Eq (kvarh)
Other: Power Factor (PF), Frequency (Hz), %THD, Demand.
Display Backlit graphical LCD.
Local Interface Keypad with navigation and function keys.
Standard Communication 1 x USB (Type-B) port for PC connection using ABB ETU Set software.
Optional Communication Modules Plug-in modules for:
• CM-MPU: Modbus RTU (RS-485)
• CM-PPU: Profibus DP
• CM-EPU: Ethernet (Modbus TCP)
Event Recording Logs last fault events (cause, date/time, phase currents).
Ambient Temperature -25°C to +70°C (operation)
Standards IEC 60947-2, IEC 61557-12
The ABB PR222MP is an advanced Electronic Trip Unit (ETU) designed for ABB's Tmax XT series Molded Case Circuit Breakers (MCCBs) in the T4 to T7 frame sizes. It represents a significant upgrade from basic thermal-magnetic protection, offering a comprehensive suite of protection, measurement, and communication functions in a single, integrated unit. The "MP" suffix highlights its two core capabilities: M for advanced Measurement and energy metering, and P for Protection configurability via a front keypad.