Technical Parameters
Parameter Specification
Product Family ABB Emax 2 E2N Series Air Circuit Breaker
Rated Current (I<sub>n</sub>) 2000 A
Number of Poles 3‑pole (3P) or 4‑pole (4P)
Rated Operational Voltage (U<sub>e</sub>) Up to 690 V AC
Rated Insulation Voltage (U<sub>i</sub>) 1000 V AC
Rated Impulse Withstand Voltage (U<sub>imp</sub>) 12 kV
Rated Short-Circuit Breaking Capacity (I<sub>cu</sub>) Up to 66 kA at 400–690 V AC
Rated Short-Time Withstand Current (I<sub>cw</sub>) ~66 kA for 1 s
Protection Releases Ekip Dip / LSIG / PR-series overcurrent releases (model dependent)
Mounting Type Fixed or withdrawable
Standards Compliance IEC 60947‑2
Typical Use Protection and switching of feeders, motors, and busbars in electrical distribution systems
The ABB E2N 2000A is a low‑voltage air circuit breaker (ACB) from ABB’s Emax 2 E2N series, engineered for electrical distribution and protection in industrial, commercial, and utility power systems. These breakers are designed to provide reliable overload, short‑circuit, and fault protection for heavy‑duty electrical installations.