Technical Specifications
Specification Value
Manufacturer ABB
Model / Part Number T5S630 PR221DS‑LS/I R630 P MP 3P
Product Type Molded Case Circuit Breaker (MCCB)
Series Tmax T5
Number of Poles 3 Pole (3P)
Rated Uninterrupted Current (Iu) 630 A
Rated Operational Voltage Up to 690 V AC
Rated Insulation Voltage (Ui) 1000 V
Rated Impulse Withstand Voltage (Uimp) 8 kV
Trip Unit Type PR221DS‑LS/I (electronic long‑time, short‑time and instantaneous protection)
Short‑Circuit Performance Level S
Rated Ultimate Short‑Circuit Breaking Capacity (Icu) ~85 kA @ 220–230 V AC; ~50 kA @ 380–415 V AC; ~25 kA @ 690 V AC
Rated Service Short‑Circuit Breaking Capacity (Ics) Percent of Icu depending on voltage rating
Electrical Endurance ~5000 operations
Mechanical Endurance ~20,000 operations
Connection Type Fixed front (bolt) terminals
Power Loss (Per Pole) ~41 W
Operating Temperature Range Standard industrial range
Degree of Protection IP20 (installed)
Standards Compliance IEC 60947‑2 and related molded case breaker standards
Typical Applications Main and distribution circuit protection, industrial power panels, motor feeder protection
The ABB T5S630 PR221DS‑LS/I R630 P MP 3P is a heavy‑duty three‑pole molded case circuit breaker (MCCB) from ABB’s Tmax T5 series, designed to provide reliable protection and switching for low‑voltage electrical distribution systems. It incorporates an electronic trip unit (PR221DS‑LS/I) offering adjustable thermal and magnetic protection with performance level S, suitable for protecting circuits and electrical equipment from overloads, short circuits, and fault conditions. The breaker has a fixed installation style with front connection terminals and robust construction for industrial, commercial, and power distribution applications.