Technical Specifications
Specification Value
Manufacturer ABB
Model / Part Number OVR T2 3N 80‑275S P TS QS (also 2CTB815708R0800)
Product Type Surge Protective Device (SPD), Type 2
Protection Purpose Protection against transient overvoltages, lightning and switching surges
Number of Poles Protected 4 (3 phases + Neutral)
Rated Voltage (Uᵣ) 230 V AC
Nominal System Voltage (Uₒ) 230 / 400 V AC
Maximum Continuous Operating Voltage (U₍c₎) 275 V AC
Voltage Protection Level (Uₚ) ~1.4 kV (L‑N, N‑PE)
Surge Current Rating (8/20 µs) Max. 80 kA total
Nominal Discharge Current (8/20 µs) 20 kA
Impulse Current (10/350 µs) ~6.25 kA
Rated Service Short‑Circuit Capacity (Iₛₙ) Up to 100 kA
Protection Class Class II
Standards Compliance IEC 61643‑11 / EN 61643‑11
Mounting DIN‑rail (35 mm)
Protection Degree IP20
Operating Temperature Range −40 °C to +80 °C
Auxiliary Contacts 1 NO + 1 NC (for remote signalling)
Status Indicators Visual indicators for each protection module
Auxiliary Circuit Load Min. 12 V DC @10 mA, Max. 250 V AC @1 A
Typical Use Surge protection for three‑phase electrical distribution systems
The ABB OVR T2 3N 80‑275S P TS QS is a Type 2 surge protective device (SPD) designed to protect low‑voltage electrical systems from transient overvoltages caused by lightning strikes and switching surges. It is intended for installation near the service entrance or load distribution point on a DIN‑rail and is compatible with three‑phase TN‑S and TT power distribution systems. The device features multiple protection stages to divert surge energy safely to ground, limiting the voltage seen by downstream equipment. It incorporates visual and auxiliary signalling for operational and maintenance feedback and is suitable for residential, commercial, and industrial distribution panels where enhanced surge protection is required.