Parameter Specification
Product Line / Series System Pro M compact S200 (S200 Series)
Device Type Miniature Circuit Breaker (MCB) with B Curve
Poles 3P (Three Poles)
Rated Current (Iₙ) 6 A (per pole)
Rated Voltage (Uₙ) 400 V AC (3-phase)
Rated Frequency 50/60 Hz
Breaking Capacity (Icn) 6 kA (at 400V AC). This is the standard value for the base S200 series.
Tripping Characteristic B Curve (Instantaneous magnetic trip operates between 3 to 5 times Iₙ, i.e., between 18A and 30A per pole). This provides fast, sensitive protection ideal for circuits with long cable runs or where limiting let-through energy is critical.
Mechanical Endurance ≥ 20,000 operations
Electrical Endurance ≥ 10,000 operations (at Iₙ)
Mounting 35 mm symmetrical DIN rail (EN 60715)
Width 54 mm (3 standard modules, each 18mm)
Terminal Torque 1.5 - 2.0 Nm (for rated cross-section conductors)
Connection Capacity Rigid Cable: Up to 25 mm² (per pole)
Flexible Cable: Up to 16 mm² (with ferrule recommended, per pole)
Standards Compliance IEC/EN 60898-1, IEC/EN 60947-2
Ambient Temperature (Operation) -25°C to +55°C
The ABB S203-B6 is a three-pole miniature circuit breaker (MCB) from the industry-standard S200 series, featuring a "B" characteristic trip curve.
This device is a compact, three-module MCB with a rated current of 6 Amperes per pole. The "B" curve is designed for the protection of circuits with very low inrush currents, providing fast and sensitive protection against short-circuits. It is the standard choice for circuits supplying purely resistive loads or loads with minimal startup surge, such as general lighting, socket outlets for small appliances, and certain control circuits.