Parameter Specification
Device Type Rotary Isolator Switch / Disconnector (Load Break Switch)
Product Series MJ / MJS Series
Rated Operational Current (Ie) 60 A (at AC-22A / AC-23A duty)
Number of Poles 4 Poles (3P + N) (Based on common "B" variant coding. Other variants exist, e.g., "A" for 3P, "C" for 2P). Must be confirmed on the device or datasheet.
Rated Insulation Voltage (Ui) 690 V
Rated Operational Voltage (Ue) 400 V AC / 500 V AC
Utilization Category AC-22A (Switching of mixed resistive and inductive loads).
AC-23A (Switching of motor loads or other highly inductive loads).
Rated Making & Breaking Capacity Typically 10 x Ie (600 A) for AC-23A at 400V.
Short-Time Withstand Current (Icw) Typically 10 kA for 1 second (ensures it can withstand fault currents without damage).
Mechanical Durability ≥ 10,000 operations
Electrical Durability ≥ 5,000 operations (at rated current)
Control Method Manual rotary operation via handle. Handle is often detachable and can be padlocked in the OFF position (up to 3 padlocks).
Mounting Mounts directly onto a panel or enclosure door via a mounting kit. The switch body is mounted behind the panel.
Terminal Type Screw clamp terminals.
Terminal Connection Capacity Typically up to 35 mm² (for 60A model).
Protection Degree Switch body: IP00 (must be installed inside an enclosure).
With handle mounted on door: Typically achieves IP54 or higher for the front.
Ambient Temperature (Operation) -25°C to +60°C
Standards Compliance IEC/EN 60947-1, IEC/EN 60947-3
The ABB MJS2-60B is a high-quality rotary isolator switch, also commonly known as a disconnector or load break switch, from ABB's MJ/MJS series of manual control and switching devices. It serves as a main switch or functional isolator in electrical distribution boards and industrial enclosures.