Technical Parameters
General & Contact Configuration
Product Type: Electromechanical contactor
Series: ASL16
Number of Main Poles: 3 (three‑phase)
Main Contact Configuration: 3 Normally Open (3 NO)
Built‑In Auxiliary Contact: 1 Normally Open (1 NO)
Control Circuit Type: DC coil (polarity sensitive)
Electrical Ratings
Rated Operational Voltage (Main Circuit): up to 690 V AC
Rated Operational Voltage (Control Coil): DC (e.g., 220 V DC)
Rated Operational Current (AC‑1):
30 A @ 690 V AC at 40 °C ambient
26 A @ 690 V AC at 70 °C ambient
Rated Operational Current (AC‑3 – Motor Control):
18 A @ 220–415 V AC
15 A @ 500 V AC
10.5 A @ 690 V AC
Coil & Control
Coil Type: DC magnet coil
Control Voltage: Specified DC voltage variant (220 V DC typical for “88” suffix)
Coil Polarity: Polarity must be respected for DC operation
Insulation & Withstand
Rated Insulation Voltage (Ui): 690 V AC
Rated Impulse Withstand Voltage (Uimp): 6 kV
Conventional Free‑Air Thermal Current (Ith): 35 A @ 40 °C
Mechanical & Mounting
Terminal Type: Screw terminals
Mounting: DIN‑rail or panel mount compatible
Mechanical Durability: High cycle life typical for ASL contactors
Dimensions: 45 mm (W) × 77 mm (D) × 86 mm (H)
Net Weight: ~0.30 kg
Environmental
Operating Ambient Temperature: −25 °C to +60 °C (with thermal overload)
Without overload: −40 °C to +70 °C
Pollution Degree: 3
Protection: IP20 (installed inside panel)
The ABB ASL16‑30‑10‑88 is a compact and reliable electromechanical contactor designed for switching and controlling three‑phase power circuits in industrial and commercial electrical systems. It belongs to the ABB ASL16 series of contactors, which are typically used for controlling motors, resistive loads, and general power circuits up to 690 V AC or 220 V DC. The contactor features a block‑type design with three main poles and a built‑in auxiliary contact for control logic or signaling feedback.