Technical Parameters
Electrical Ratings
Rated Current (In): 2 A
Number of Poles: 2P (two poles)
Tripping Characteristic: C‑curve (suitable for moderate inrush loads)
Rated Operational Voltage (Ue):
Up to 400 V AC (IEC 60898‑1)
Up to 440 V AC (IEC 60947‑2)
Rated Insulation Voltage (Ui): 440 V
Rated Frequency: 50 / 60 Hz
Rated Short‑Circuit Breaking Capacity (Icn): 10 kA at 230/400 V AC
Rated Ultimate Short‑Circuit Breaking Capacity (Icu): up to 15 kA
Current Limiting Class: 3
Overvoltage Category: III
Rated Impulse Withstand Voltage (Uimp): 4 kV
Operational Voltage Range: 12 V AC/DC to 440 V AC
DC Interrupting Capability: Up to approx. 125 V DC
Mechanical & Mounting
Mounting: Standard DIN‑rail (35 mm)
Terminal Type: Screw terminals
Tightening Torque: Approx. 2 N·m
Mechanical Endurance: ~20,000 operations
Electrical Endurance: ~20,000 AC cycles
Housing Material: High‑quality insulating material (light grey)
Contact Position Indication: Red (ON) / Green (OFF) indicators
Environmental
Ambient Operating Temperature: approx. ‑25 °C to +55 °C
Pollution Degree: 3
Protection Rating: IP20 (when mounted in panel/enclosure)
Mounting Position: Any
The ABB S202‑C2 is a compact 2‑pole miniature circuit breaker from the ABB System pro M circuit breaker range, designed to provide reliable overload and short‑circuit protection in low‑voltage electrical distribution systems. This breaker integrates a thermal trip for overload protection and a magnetic trip for short‑circuit protection, ensuring safety and reliability in various applications.