Technical Parameters
General & Electrical Ratings
Product Type: Electromechanical Contactor (DC operated)
Series: ASL09
Number of Poles: 3 main poles
Auxiliary Contacts: 1 normally closed (1 NC) built‑in auxiliary contact
Rated Control Circuit Voltage (Uc): DC 110 V
Rated Operational Voltage (Main Circuit): up to 690 V AC / up to 690 V AC environment rating
Rated Insulation Voltage (Ui): 690 V
Rated Impulse Withstand Voltage (Uimp): 6 kV
Control & Coil
Coil Type: DC coil designed for low consumption
Coil Operating Voltage: 110 V DC
Control Frequency: n/a (DC coil)
Operational Performance
Conventional Free‑Air Thermal Current (Ith): ~22 A
Rated Operational Current (AC‑1): ~22 A at 690 V AC (temperature‑dependent)
Rated Operational Current (AC‑3):
~9 A at 220–415 V AC
~8 A at 440–500 V AC
~5–7 A at 690 V AC
Rated Operational Power (AC‑3):
~2.2 kW @ 220–240 V AC
~4–5.5 kW @ 400–690 V AC
Rated Operational Current (AC‑15 Control):
~4 A @ 220–240 V AC
~2–3 A @ 380–690 V AC
Rated Operational Current (DC‑13):
~0.55–1.1 A @ 110–125 V DC
~0.27 A @ 220–250 V DC
~2.8 A @ 400 V DC
~1–2.8 A @ 250–500 V DC
Switching & Endurance
Mechanical Switching Frequency: Up to ~3600 cycles/hour
Electrical Switching Frequency:
AC‑1: ~600 cycles/hour
AC‑15 / AC‑3: ~1200 cycles/hour
DC‑13: ~900 cycles/hour
Operate/Release Times: ~7–21 ms to open/close contacts on coil energization/de‑energization
Mechanical & Connection
Terminal Type: Screw terminals
Wire Stripping Length: ~9 mm
Connecting Capacity: Designed for standard control and power wiring sizes
Environmental & Physical
Ambient Operating Temperature: −40 °C to +70 °C (varies with relay or overload fitted)
Storage Temperature: −60 °C to +80 °C
Degree of Protection: IP20 at terminals
Maximum Permissible Altitude: ~3000 m
Approx. Dimensions: ~45 mm (W) × ~68 mm (H) × ~72.5 mm (D)
Net Weight: ~0.28 kg
The ABB ASL09‑30‑01‑86 is a compact 3‑pole contactor designed for control and switching of three‑phase power circuits in industrial and commercial applications. It belongs to the ABB ASL09 series of contactors optimized for DC coil operation and is suitable for controlling motors, resistive and inductive loads. This contactor features a robust block‑type construction with three main contacts and a built‑in auxiliary contact, enabling both load switching and interface with control logic or feedback systems.