Technical Parameters
Electrical Ratings
Rated Current (In): 3 A (C‑curve)
Number of Poles: 2P (two poles)
Rated Operational Voltage: up to 400 V AC (IEC standards) / 440 V AC
Rated Insulation Voltage (Ui): 440 V
Rated Frequency: 50 / 60 Hz
Rated Short‑Circuit Breaking Capacity (Icn): 10 kA at 230/400 V AC
Rated Ultimate Breaking Capacity (Icu): up to 15 kA
Current Limiting Class: 3
Overvoltage Category: III
Rated Impulse Withstand Voltage (Uimp): 4 kV
Operational Voltage Range: 12 V AC/DC — 440 V AC (typical)
DC Interrupting Capability (approx.): up to 125 V DC
Contact Position Indication: Red “ON” / Green “OFF”
Mechanical & Installation
Mounting: Standard DIN‑rail (TH35) mounting
Terminal Type: Screw terminals with bi‑directional cylinder‑lift design
Tightening Torque: ~2 N·m
Mechanical Endurance: ~20,000 operations
Electrical Endurance: ~20,000 AC cycles
Mounting Position: Any orientation allowed
Housing Material / Color: Group II insulation, RAL 7035 light grey
Auxiliary Accessories: Compatible with bottom‑fitting auxiliary contacts and other add‑ons in the S200M range
Environmental & Physical
Ambient Operating Temperature: approximately ‑25 °C to +55 °C
Pollution Degree: 3
Protection: IP20 (with enclosure)
Dimensions (approx.):
Width: 2 modules (~35 mm)
Height: ~88 mm
Depth: ~69 mm
Weight: ~0.25 kg
The ABB S202M‑C3 is a 2‑pole miniature circuit breaker from the ABB System pro M compact S200M series, designed for reliable overcurrent protection in low‑voltage electrical installations. It provides both thermal overload protection and magnetic short‑circuit protection in a single compact device.