Technical Parameters
Electrical Ratings
Product Type: Molded Case Circuit Breaker (MCCB)
Frame Rated Current (Iu): 160 A
Number of Poles: 3
Trip Unit Type: Thermal-Magnetic (TMD)
Adjustable Thermal Setting Range: 17.5 … 25 A
Instantaneous Magnetic Setting (Ii): 300 A
Rated Operational Voltage: up to 690 V AC / 500 V DC
Rated Insulation Voltage (Ui): 1000 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Frequency: 50 / 60 Hz
Conventional Free-Air Thermal Current: 160 A
Rated Service Short-Circuit Breaking Capacity (Ics):
85 kA at 220-240 V AC
50 kA at 380-415 V AC
36 kA at 500 V AC
25 kA at 525 V AC
12 kA at 690 V AC
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
Same as Ics for corresponding voltages
Short-Circuit Performance Level: S
Mechanical & Installation
Mounting Type: Fixed
Terminal Connection: Front terminals with bolt/lug type connections
Recommended Tightening Torque: ~6 N·m
Connecting Capacity: Compatible with busbar up to 32.5 … 100 mm²
Electrical Durability: ~8000 operations
Mechanical Durability: ~25,000 operations
Environmental & Physical
Operating Temperature: Standard industrial ambient range
Standards Compliance: IEC 60947-2 series
Compact Size: Typical MCCB form factor for panel and distribution use
The ABB XT2S 160 TMD 25-300 3P F F is a high-performance molded case circuit breaker (MCCB) designed for protection of low-voltage power distribution systems and industrial electrical installations. It combines thermal and magnetic trip elements in the TMD trip unit to provide reliable overload and short-circuit protection.