Technical Parameters
Electrical Ratings
Type: Electronic overload relay
Number of Poles: 3
Current Setting Range: 5.7 to 18.9 A
Trip Class Options: Class 10E, Class 20E, Class 30E
Auxiliary Contact Configuration: 1 NO (signal) + 1 NC (trip)
Rated Operational Current: up to 18.9 A
Rated Insulation Voltage (Ui): 690 V AC
Rated Operational Voltage: up to 690 V AC
Rated Impulse Withstand Voltage (Uimp): 6 kV
Frequency: 50/60 Hz
Protection & Performance
Motor Protection: Overload protection with phase failure detection
Reset Function: Automatic and/or manual reset options
Temperature Compensation: Included for accurate trip behavior across temperature range
Trip-Free Mechanism: Prevents weld-on in overload trip condition
Test and Stop Functions: Built-in test and stop operation for safe maintenance
Mechanical & Installation
Mounting: Designed to be paired directly with compatible contactors
Terminal Type: Screw terminals for main and auxiliary connections
Protection Rating: IP20
Pollution Degree: 3
Dimensions: Approx. 74.6 mm (H) × 44.4 mm (W) × 57 mm (D)
Weight: Approx. 0.15 kg
Environmental
Operating Ambient Temperature: –25°C to +70°C
Storage Temperature: –50°C to +85°C
Maximum Service Altitude: ~2000 m
Standards & Compliance
IEC/EN 60947-1
IEC/EN 60947-4-1
IEC/EN 60947-5-1
UL 60947-1 / UL 60947-4-1
The ABB E16DU18.9 is a compact electronic overload relay designed to provide reliable overload and phase-failure protection for three-phase motor circuits. It is self-powered (no external supply required) and combines advanced electronic sensing with adjustable trip characteristics for precise motor protection. With a wide current setting range and selectable trip class, this model adapts to various motor sizes and industrial applications. The relay includes auxiliary contacts for signaling and is suitable for use with compatible ABB contactor frames in control panels and motor starter assemblies.