Technical Parameters
Parameter Specification
Series ABB CL / HomeLine / DS200 Series
Product Type 2-Pole (1P+N) RCBO with Overcurrent & Residual Current Protection
Order Code CL2-507R
Number of Poles 2-Pole (1P+N) – Both phase and neutral are switched, but only the phase pole has overcurrent protection.
Rated Current (In) 16 Amperes (The standard current rating associated with the "CL2-5" base model. Other ratings like 10A, 20A, etc., have different suffixes).
Tripping Characteristic C-Curve
Rated Residual Operating Current (IΔn) 30 mA (0.03 A)
Residual Current Type Type AC (for sinusoidal alternating residual currents)
Rated Short-Circuit Breaking Capacity (Icn) 10 kA (at 230/400V AC)
Rated Operational Voltage (Ue) 230V AC (Single-Phase)
Rated Insulation Voltage (Ui) 400V AC
Trip Time at IΔn ≤ 0.3 seconds
Trip Time at 5x IΔn (150 mA) ≤ 0.04 seconds
Test Button Yes (typically yellow), for periodic testing of the RCD function.
Mounting DIN Rail (35mm) mounting.
Terminals Screw terminals suitable for solid and stranded conductors.
Module Width 2 modules (36mm).
Standards Compliance IEC/EN 61009-1 (Primary standard for RCBOs)
Ambient Temperature -25°C to +60°C (Operation)
The ABB CL2-507R is a 2-pole (1P+N), C-curve, 10 kA breaking capacity, Residual Current Circuit Breaker (RCBO). It belongs to the ABB CL (Circuit breaker Line) series, also commonly known as the "HomeLine" or DS200 series in some markets, designed for residential, commercial, and light industrial final circuit protection.