Technical Parameters
General
Product Type: Contactor relay / auxiliary contactor
Model: NF22E‑13
Poles: 4 poles (4P)
Contact Configuration: 2 × Normally Open (NO) + 2 × Normally Closed (NC) auxiliary contacts
Mounting / Terminal Type: Screw terminal connections
Design: Block type relay suitable for industrial panels
Control / Coil
Rated Control Supply Voltage: 100 … 250 V AC/DC
Rated Frequency: 50 / 60 Hz (for AC coils)
Coil Operation: AC/DC compatible within the specified range
Electrical Ratings
Rated Operational Voltage (Main/Auxiliary Circuits): Up to 690 V
Rated Insulation Voltage (Ui): Up to 690 V (IEC) / 600 V (UL/CSA)
Conventional Free‑air Thermal Current (Ith): 16 A
Rated Operational Current AC‑15:
6 A @ 24 / 127 V AC
4 A @ 220 / 240 V AC
3 A @ 400 / 440 V AC
2 A @ 500 / 690 V AC
Rated Operational Current DC‑13:
6 A @ 24 V DC
2.8 A @ 48 V DC
1 A @ 72 V DC
0.55 A @ 110 / 125 V DC
0.27 A @ 220 / 250 V DC
0.15 A @ 400 V DC
0.13 A @ 500 V DC
0.1 A @ 600 V DC
Short‑time Withstand Current (Icw):
~140 A for 0.1 s
~100 A for 1 s
Performance
Maximum Electrical Switching Frequency:
AC‑15: ~1200 cycles/hour
DC‑13: ~900 cycles/hour
Maximum Mechanical Switching Frequency: ~6000 cycles/hour
Physical & Dimensions
Width: ~45 mm
Depth / Length: ~77 mm
Height: ~86 mm
Net Weight: ~0.27 kg
Environmental & Protection
Operating Ambient Temperature: −40 °C to +70 °C
Storage Temperature: −60 °C to +80 °C
Rated Impulse Withstand Voltage (Uimp): 6 kV
Terminal Protection Rating: IP20 (terminals)
Pollution Degree: Suitable for industrial environments
Maximum Operating Altitude (without derating): ~3000 m
Standards & Compliance
Conforms to IEC/EN 60947‑5‑1
Complies with UL 508 and CSA C22.2 No.14
Applications
Switching auxiliary and control circuits
Interfacing between control logic (PLC, switches) and loads
Automation control panels and machinery
Interlocking and feedback signaling
OEM and industrial control system integration
The ABB NF22E‑13 is a 4‑pole contactor relay / auxiliary contactor relay designed for industrial control and automation applications. It is used to switch auxiliary and control circuits in electrical panels, machinery and control systems. The relay features two Normally Open (NO) and two Normally Closed (NC) contacts, enabling flexible control and feedback functions in automation logic or interlock circuits. The device supports a wide coil voltage range (100–250 V AC/DC), making it suitable for use with mixed control systems that operate on either AC or DC control supplies.