Key Specifications
General
Product Type: Molded Case Circuit Breaker (MCCB)
Series: ABB SACE Tmax XT
Poles: 3
Frame/Model: XT3N250 TMD250/2500 FF
Rated Current: 250 A
Trip Unit: Thermal‑magnetic (TMD), adjustable 175–250 A
Voltage & Frequency
Rated Operational Voltage (AC): 690 V AC
Rated Operational Voltage (DC): Up to 500 V DC
Rated Frequency: 50/60 Hz
Electrical Ratings
Rated Insulation Voltage (Ui): 800 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Rated Instantaneous Short‑Circuit Setting (Ii): 2500 A
Rated Uninterrupted Current (Iu): 250 A
Breaking Capacity
Ultimate Breaking Capacity (Icu):
~50 kA at 220–240 V AC
~36 kA at 380–415 V AC
DC Breaking Capacity (poles in series):
~36 kA @ 250 V DC
~50 kA @ 500 V DC
Mechanical & Durability
Power Loss: ~17.8 W per pole
Electrical Durability: ~8 000 operations
Mechanical Durability: ~25 000 operations
Protection Class: IP20
Construction & Installation
Fixed mounting with front (FF) terminals
Suitable for industrial power distribution panels
Standards & Safety
Complies with IEC 60947‑2
CE and RoHS compliant
The ABB XT3N250 TMD250/2500 FF 3P is a 3‑pole molded‑case circuit breaker (MCCB) from ABB’s SACE Tmax XT series. It provides protection for industrial and commercial power distribution systems against overloads and short circuits. The breaker features a thermal‑magnetic (TMD) trip unit with an adjustable protection range, suitable for switchboards, motor feeds, and control panels. It is designed for fixed mounting with front terminals.