Key Technical Parameters
General & Protection Ratings
Product / Model: ABB T5H 400 TMA 400‑4000 3P MCCB
Part Number: 1SDA054445R1
Device Type: Molded Case Circuit Breaker (MCCB)
Series: Tmax T5H
Number of Poles: 3 (three‑pole)
Mounting Style: Fixed with front terminals
Trip Unit Type: Thermal‑Magnetic (TMA)
Current & Voltage Ratings
Rated Uninterrupted (Continuous) Current (In): 400 A
Overload Trip Setting Range: Adjustable around 280–400 A
Instantaneous Short‑Circuit Setting Range: ~2000 A to 4000 A
Rated Operational Voltage (AC): Up to 690 V AC
Rated Operational Voltage (DC): Up to 750 V DC
Rated Frequency: 50 Hz / 60 Hz
Rated Insulation Voltage (Ui): 1000 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Breaking Capacities
Rated Ultimate Short‑Circuit Breaking Capacity (Icu):
~100 kA at 220–230 V AC
~70 kA at 380–440 V AC
~50 kA at 500 V AC
~40 kA at 690 V AC
Rated Service Short‑Circuit Breaking Capacity (Ics):
Matches Icu values at respective voltages (e.g., 100 kA at 220–230 V AC, 70 kA at 380–440 V AC)
Durability & Performance
Electrical Durability: ~7,000 operating cycles (at 60 cycles/hour)
Mechanical Durability: ~20,000 cycles (at 120 cycles/hour)
Per‑Pole Power Loss at Rated Conditions: ~19.5 W
Mechanical & Physical
Terminal Type: Fixed front terminals
Dimensions: ~140 mm width × ~205 mm height × ~104 mm depth
Weight: ~4.8 kg
Protection Degree: Standard industrial MCCB housing suitable for enclosure use
Typical Applications
Protection of three‑phase distribution circuits in industrial and commercial installations
Feeder and motor circuit protection in switchboards
Overload and short‑circuit safeguarding in electrical distribution systems
The ABB T5H 400 TMA 400‑4000 3P MCCB is a three‑pole molded case circuit breaker (MCCB) from ABB’s Tmax T5H series. It provides fixed‑mount protection for three‑phase electrical systems and combines thermal and magnetic trip elements to guard against both overload and short‑circuit conditions in industrial and commercial power distribution. This breaker features fixed front terminals for secure panel installation and is suitable for use in switchgear, distribution boards, and motor feeder circuits requiring high‑performance circuit protection.