Key Specifications
Electrical Ratings
Model: MS132‑6.3
Function: Manual motor starter / Motor protection circuit breaker
Adjustable Current Range: 4.0 – 6.3 A (thermal overload setting)
Rated Operational Current (Ie): 6.3 A
Rated Insulation Voltage (Ui): 690 V AC / 250 V DC
Rated Operational Voltage (Ue): Up to 690 V AC (50/60 Hz)
Rated Operational Power (AC‑3): ~2.2 kW @ 400 V AC (three‑phase)
Breaking Capacity (Ics): 100 kA
Trip Class: Class 10 (thermal trip characteristic)
Protection & Functionality
Overload Protection: Adjustable thermal overload to protect motors from overcurrent.
Short‑Circuit Protection: Built‑in automatic short‑circuit interruption; no external fuse required.
Phase Failure Sensitivity: Detects loss of phase to prevent motor damage.
Disconnect Feature: Acts as a manual disconnect switch.
Mechanical & Installation
Poles: 3‑pole (3P)
Control Type: Rotary handle with ON/OFF/TRIP indicator
Handle Lockable: Yes
Mounting: Standard TH35 DIN rail compatible
Terminal Connections: Screw terminals
Environmental & Physical
Protection Rating: IP20 (finger‑safe enclosure)
Operating Temperature: −25 °C to +70 °C
Storage Temperature: −40 °C to +80 °C
Dimensions: ~45 mm width × ~90 mm height × ~86.8 mm depth
Mechanical Lifespan: ~100 000 switching cycles
Typical Applications
Motor control and protection in industrial automation systems
Protection of small motors in pumps, fans, conveyors
Manual switching and thermal protection combined in motor control panels
Applications in three‑phase and single‑phase circuits where motor protection is required
The ABB MS132‑6.3 Manual Motor Starter is a compact electromechanical protection device used for manual motor control and protection in industrial and commercial applications. It combines motor ON/OFF switching with overload, short‑circuit, and phase failure protection without requiring external fuses. The device is equipped with a rotary handle that clearly indicates the switch position (ON/OFF/TRIP) and can be locked to prevent unauthorized changes. It is designed for three‑pole (3P) applications and can be mounted on a standard DIN rail.