Technical Specifications
Parameter Specification
Part Number / Model 2CSR255180R1164
Series / Type DS201 C16 A30 RCBO
Product Category Residual Current Circuit Breaker with Overcurrent Protection
Poles 1P + N
Rated Current (In) 16 A
Rated Residual Current Sensitivity (IΔn) 30 mA
Rated Operational Voltage (Ue) 230 V AC
Rated Frequency 50–60 Hz
Residual Current Type Type A
Tripping Characteristic C curve
Rated Short‑Circuit Breaking Capacity (Icu) 10 kA
Rated Service Short‑Circuit Breaking Capacity (Ics) 7.5 kA
Rated Insulation Voltage (Ui) 500 V
Rated Impulse Withstand Voltage (Uimp) 4 kV
Overvoltage Category III
Pollution Degree 2
Number of Modular Widths 2 modules
Contact Position Indication Red ON / Green OFF
Fault Indication Blue flag on toggle
Mounting DIN‑rail (35 mm)
Terminal Type Screw terminals
Electrical Endurance ~10,000 cycles
Mechanical Endurance ~20,000 cycles
Operating Temperature −25 °C to +55 °C
Degree of Protection IP20 / IP40
Connection Capacity Solid: 0.75–25 mm², Stranded/Ferruled: 0.75–16 mm²
Standards Compliance IEC/EN 61009‑1, IEC/EN 61009‑2‑1
Color / Housing Black toggle, grey body
Weight (approx.) ~0.20 kg
Dimensions (W×H×D) ~35 mm × 85 mm × 69 mm
The ABB DS201 C16 A30 RCBO (Residual Current Circuit Breaker with Overcurrent Protection) is a compact protective device designed for single‑phase electrical circuits. It combines the functions of an overcurrent circuit breaker and a residual current device (earth leakage protection) in a single unit with a 1P+N (one pole + neutral) configuration. This RCBO provides comprehensive protection against overloads, short‑circuits, ground faults, and indirect contacts, with additional protection against direct contact through a 30 mA sensitivity. It is suitable for use in residential, commercial, and light industrial electrical distribution panels.