Technical Parameters
Parameter Specification
Product type Molded Case Circuit Breaker (MCCB)
Product family ABB SACE Tmax XT / T3N250
Poles 3 poles
Version FF – Front Fixed Terminals
Trip unit type TMD (Thermo‑magnetic)
Adjustable instantaneous short‑circuit setting Up to 2000 A
Rated uninterrupted current 250 A frame (breaker size)
Rated operational voltage Up to 690 V AC / 500 V DC
Rated insulation voltage (Ui) 800 V AC
Rated impulse withstand voltage (Uimp) 8 kV
Rated service short‑circuit breaking capacity (Ics) 50 kA @ 220–240 V AC, 36 kA @ 380–415 V AC, lower ratings at higher voltages (typical values)
Rated ultimate short‑circuit breaking capacity (Icu) Similar long‑circuit capacity depending on voltage level
Mechanical durability ~25,000 operations
Electrical durability ~8,000 operations
Rated frequency 50 / 60 Hz
Standards IEC 60947‑2 compliant
Mounting Fixed panel installation
Terminal type Front fixed with bolt connections
Typical applications Industrial/commercial power distribution, feeder protection, control panels
The ABB XT3N 250 TMD 200‑2000 3P FF is a three‑pole molded case circuit breaker (MCCB) from ABB’s SACE Tmax XT/T3N series, designed for protection and manual switching in industrial and commercial low‑voltage power systems. It features a thermo‑magnetic (TMD) trip unit with adjustable instantaneous/short‑circuit setting up to 2000 A, delivering reliable protection against overload and short‑circuit faults. The breaker’s front fixed terminals simplify panel mounting and wiring, and its robust design ensures dependable performance in power distribution and feeder protection applications.