Technical Parameters
Parameter Specification
Product type Molded Case Circuit Breaker (MCCB)
Product series ABB SACE Tmax T2H
ABB Ordering Code 1SDA051041R1
Poles 3 poles
Terminal type Front fixed terminals
Trip unit type TMD (Thermal‑magnetic)
Current setting range 32–500 A
Rated uninterrupted current (Iu) 160 A frame rating
Rated operational voltage (Ue) 690 V AC / 500 V DC
Rated insulation voltage (Ui) 800 V
Rated impulse withstand voltage (Uimp) 8 kV
Breaking capacity – service (Ics) 100 kA @ 220–230 V AC / 70 kA @ 380–415 V AC / 55 kA @ 440 V AC / 36 kA @ 500 V AC / 8 kA @ 690 V AC
Ultimate breaking capacity (Icu) Same as service values depending on voltage
Protection functions Overload and short‑circuit protection
Standards compliance IEC 60947‑2
Mechanical durability ~25,000 operations
Electrical durability ~8,000 operations at rated conditions
Power loss per pole ~2.7 W at rated load
Mounting Panel fixed installation
Typical applications Industrial and commercial power distribution protection
The ABB 1SDA051041R1 is a three‑pole molded case circuit breaker from ABB’s SACE Tmax T2H range with front fixed terminals and a thermal‑magnetic trip unit. It is designed to protect low‑voltage electrical distribution circuits from overload and short‑circuit faults while providing reliable switching in industrial and commercial applications. The breaker features adjustable trip settings and robust construction to ensure dependable performance in power distribution systems.