Technical Data
Parameter Value / Description
Manufacturer Part Number 1SFL647001R7011
Product Line ABB OVR Surge Protective Device
Type / Class Type 2 Surge Arrester (Tested according to IEC/EN 61643-11)
Rated Voltage (Un) 230/400V (for 50/60Hz AC systems)
Maximum Continuous Operating Voltage (Uc) 320 V AC (between Line and Neutral). This is the voltage it can withstand continuously.
Protection Level (Up) @ In ≤ 1.5 kV (measured at the rated discharge current In). This is the key parameter defining its clamping performance.
Nominal Discharge Current (In) 8/20 µs 20 kA (per pole). Standard test current representing its duty cycle.
Maximum Discharge Current (Imax) 8/20 µs 40 kA (per pole). The maximum single surge current it can handle once.
Response Time < 25 ns
Backup Fuse Recommendation Typically 63A gL/gG or as per local regulations. Must be verified in the installation manual.
Number of Poles / Connection 1P (Single Pole, for protection of one phase line to neutral/earth). Multiple units are used for multi-phase systems.
Technology Varistor-based (Metal Oxide Varistor - MOV).
Status Indicator Visual window (Green = OK, Red = Fault/End-of-Life).
Thermal Protection Integrated thermal disconnector.
Mounting DIN-rail mounted (35 mm standard rail).
Width 1 module (18 mm on a standard DIN rail).
Standards & Certifications IEC/EN 61643-11, CE marked.
The ABB 1SFL647001R7011 is a Type 2 Surge Protective Device (SPD) from the widely used OVR product family. It is designed for installation in secondary distribution boards (sub-distribution or final distribution level) within a building's electrical installation.