Technical Specifications
Parameter Value / Description
Series / Frame AF210‑30
Poles (Main Contacts) 3 poles, 3 NO (normally open)
Auxiliary Contacts 1 NO + 1 NC
Coil (Control) Voltage U<sub>c</sub> 100–250 V AC 50/60 Hz or 100–250 V DC
Rated Main‑Circuit Voltage up to 690 V AC
Conventional Free‑air Thermal Current (I<sub>th</sub>) 350 A (open contactor, 40 °C)
Rated Operational Current AC‑1 (I<sub>e</sub>) 350 A @ 690 V (40 °C); 300 A @ 690 V (55 °C); 240 A @ 690 V (70 °C)
Rated Operational Current AC‑3 (I<sub>e</sub>) 210 A @ 415/440/500/690 V (55 °C) (also 210 A at 380/400 V or 220–240 V)
Rated Power (AC‑3, P<sub>e</sub>) 59 kW @ 220–240 V; 110 kW @ 380–415/440 V; 132 kW @ 500 V; 160 kW @ 690 V
Main‑circuit connection / terminal type Bar‑type main contacts (suitable for rigid Cu or Al cable or bus bars)
Mechanical endurance / durability ~5,000,000 mechanical cycles
Size / Dimensions (approx.) Width 140 mm × Depth 180.5 mm × Height 227 mm
Ambient Operating Temperature With thermal overload relay: –25 °C … +55 °C; Without overload relay: –40 °C … +70 °C
Insulation / Rated Insulation Voltage (U<sub>i</sub>) 1000 V (IEC standard), 600 V (UL/CSA)
Auxiliary circuits wiring Auxiliary circuit terminals: flexible 1–4 mm² or solid cables; main circuits support large cross‑section bars/cables
The AF210‑30 is a 3‑pole AC contactor from ABB’s AF series, designed for industrial power circuits and three‑phase motor control / switching applications.It features 3 main contacts (normally open) for the main circuit, and includes auxiliary contacts (typically 1 NO + 1 NC) for control or signaling circuits.The contactor supports a wide‑range coil (control) voltage — for example 100–250 V AC/DC depending on coil version.The design supports robust connection via bar‑type main‑circuit terminals, suitable for heavy‑duty wiring (e.g. rigid copper/aluminum cables or bars).Suitable for motor starters, isolation / bypass / distribution circuits and general industrial loads under rated voltage/current conditions.