Technical Specifications
Parameter Value
Model / Part Number AX370‑30‑11‑84
Poles (Main Contacts) 3‑pole (3 Normally Open)
Auxiliary Contacts 1 NO + 1 NC
Control (Coil) Voltage (Uc) 110 V AC 50 Hz or 110–120 V AC 60 Hz
Rated Main Circuit Voltage Up to 1000 V AC
Conventional Free‑air Thermal Current (Ith) 250 A
Rated Operational Current AC‑1 (Ie) 600 A @ 690 V (40 °C)
500 A @ 690 V (55 °C)
400 A @ 690 V (70 °C)
Rated Operational Current AC‑3 (Ie) 370 A @ 415–440 V / 380–400 V / 220–240 V
315 A @ 500–690 V
Rated Operational Power AC‑3 (Pe) 200 kW @ 415–400 V
250 kW @ 500 V
315 kW @ 690 V
110 kW @ 220–240 V
Making / Breaking Capacity (AC‑3) Making: 10 × Ie
Breaking: 8 × Ie
Short‑time Withstand Current (Icw) 1 s → 3700 A; 10 s → 2960 A; 1 min → 1208 A; 15 min → 600 A
Rated Insulation Voltage (Ui) 690 V
Impulse Withstand Voltage (Uimp) 8 kV
Maximum Electrical Switching Frequency 300 cycles/hour
Maximum Mechanical Switching Frequency 300 cycles/hour
Degree of Protection (Auxiliary Terminals) IP40
Terminal Type (Main Circuit) Bar-type terminals
Ambient Air Temperature (with thermal overload relay) –25 °C … +55 °C
Ambient Air Temperature (without overload relay / storage) –40 °C … +70 °C
The AX370‑30‑11‑84 is a 3‑pole AC contactor from ABB’s AX series, intended for heavy‑duty industrial power switching and three‑phase motor control applications.It has 3 main contacts (normally open) and built‑in auxiliary contacts (1 NO + 1 NC), enabling additional control or feedback circuits.The control (coil) circuit supports 110 V AC at 50 Hz or 110–120 V AC at 60 Hz, compatible with standard control-voltage supplies.Its block‑type design allows for integration with add‑on auxiliary contact blocks and a variety of accessories, suitable for use in motor starters or industrial control panels.