Technical Specifications
Parameter / Item Value / Description
Product / Model CT‑ERS.22 ON‑delay Timer Relay
Part Number 1SVR630100R3300
Supply / Control Voltage (Us) 24–48 V DC or 24–240 V AC (50/60 Hz)
Function (Timer Type) Single‑function ON‑delay (delay‑on‑make)
Time Range (adjustable) Ten selectable ranges: 0.05 s … 300 h (e.g. 0.05–1 s, 0.15–3 s, 0.5–10 s, 1.5–30 s, 5–100 s, 15–300 s, 1.5–30 min, 15–300 min, 1.5–30 h, 15–300 h)
Reset / Recovery Time (after supply removal) < 80 ms
Output Contacts 2 × change‑over contacts (SPDT / 2 c/o)
Contact Ratings 250 V AC / 4 A (for general AC‑12 loads)
230 V AC / 3 A (inductive / motor‑control AC‑15 loads)
24 V DC / 4 A (DC‑12)
24 V DC / 2 A (DC‑13)
Minimum Switching Capacity 12 V / 10 mA (suitable for low‑power / signal loads)
Connection / Terminal Type Double‑chamber cage screw‑terminals (wired conductors: flexible 0.5–2.5 mm² or rigid up to 4 mm²)
Module / Mounting Dimensions Width: 22.5 mm; nominal module; DIN‑rail mount (standard TH35); easy snap‑on / removal
Overall Dimensions (W × H × D) 22.5 mm × 85.6 mm × 103.7 mm
Net Weight ~ 0.121 kg
Ambient Operating Temperature –25 °C … +60 °C
Storage Temperature Range –40 °C … +85 °C
Insulation & Withstand Ratings Rated insulation up to 500 V (input‑output); output circuit rating up to 300 V; impulse withstand voltage specified for output circuits; pollution degree 3; overvoltage category III
Certifications / Approvals Compliant with IEC/EN 61812‑1; UL 508 / CAN/CSA C22.2 No.14; CE, CB, CCC etc.; housing material UL 94 V‑0 rated
Indicators / Controls Front‑face rotary selector for time-range, internal fine‑adjust potentiometer for delay time; 2 LEDs for status indication (power / timing and output relay status)
Other Features Wide supply‑voltage flexibility (AC or DC), selectable time-range, compact DIN‑rail mounting, screw‑terminal connections, dual SPDT outputs — suitable for broad range of timing and control applications
The ABB CT‑ERS.22 is a compact, single‑function electronic ON‑delay timer relay. When control supply voltage is applied, the relay waits for a user‑selected delay time, then changes its output contacts from their default state. Its slim 22.5 mm width and DIN‑rail mountable housing make it suitable for installation in control panels, automation cabinets, and other industrial or commercial electrical control systems. The relay supports a wide supply‑voltage range, accommodates many delay‑time settings, and uses SPDT (change‑over) contacts to control downstream loads or contactors, making it a versatile timing device for automation, motor control, lighting, sequential logic, and general‑purpose time‑delay applications.