Parameters
Category Parameter Specification / Interpretation for 266DSH BSHA1B2L1TB
General Model Series 2600T Series (DST - Differential Pressure Smart Transmitter)
Type Smart dP Transmitter with Local Operator Interface
Output 4-20 mA DC, Two-wire, HART Protocol.
Measurement Performance Measured Variable Differential Pressure (dP)
Calibrated Span (BSHA1) Defined by core code. Example: 0 to 40 kPa (0.4 bar). Must be verified from official datasheet.
Reference Accuracy ±0.075% of calibrated span (Typical).
Long-Term Stability ±0.1% of URL per year.
Turndown Ratio Up to 100:1 (Software configurable).
User Interface Local Display (L1) Backlit LCD.
Local Controls Push Buttons (for configuration and navigation).
Electrical Supply Voltage 10.5 to 45 V DC (Two-wire).
Load Limit R_L ≤ (Vs - 10.5V) / 0.022 A (Ω).
Communication HART Protocol (Bell 202 FSK).
Process Connections & Materials Wetted Parts (BSH) Isolating Diaphragms & Process Connections: 316L Stainless Steel (Standard).
Fill Fluid Silicone Oil (Standard) or Inert Fluorocarbon (for O2/aggressive service).
Pressure Ports 1/4" NPT or G1/2" female (Common).
Static Pressure Rating Up to 16 MPa (2320 psi).
Mechanical & Environmental Housing Stainless Steel, Flameproof (Ex d) enclosure.
Protection Degree IP66 / IP67 / NEMA 4X.
Process Temperature -40°C to +120°C (Standard fill fluid).
Ambient Temperature -40°C to +85°C.
Certifications & Safety Explosion Protection (TB) ATEX / IECEx: Ex d IIC T4/T6 Gb (Flameproof) & Ex ia IIC T4/T6 Ga (Intrinsic Safety) - Dual Certification.
Functional Safety SIL 2/3 capable.
The ABB 266DSH BSHA1B2L1TB is a differential pressure transmitter designed for high-precision measurement in demanding industrial applications. As part of ABB’s 266DSH series, this transmitter combines robust construction, long-term stability, and advanced diagnostic capabilities for reliable operation in liquids, gases, or steam.