Parameters
Category Parameter Specification for S262-C16
General Product Type 2-Pole Miniature Circuit Breaker (MCB)
Series System Pro M compact® S200
Poles 2 Poles (2P)
Rated Current (In) 16 A per pole
Tripping Characteristic "C" Curve (per pole)
Electrical Ratings Rated Operational Voltage (Ue) AC 230/400 V (Between poles: 400V)
Rated Insulation Voltage (Ui) 500 V
Rated Frequency 50/60 Hz
Breaking Capacity Rated Service Short-Circuit Breaking Capacity (Ics) 6 kA (at 230/400V AC, per IEC/EN 60898-1)
Rated Ultimate Short-Circuit Breaking Capacity (Icu) 6 kA
Tripping Characteristics (IEC 60898) Overload (Thermal) per pole 1.13 x In (18.1A): No trip within 1 hour.
1.45 x In (23.2A): Must trip within 1 hour.
Magnetic Instantaneous Trip per pole 5 x In (80A) to 10 x In (160A).
Mechanical & Operational Electrical Life ≥ 10,000 operations (at In)
Mechanical Life ≥ 20,000 operations
Operation Single, common toggle lever for simultaneous operation of both poles.
Terminals Terminal Type Cage Clamp (Spring Loaded)
Acceptable Conductor Size Solid/Fine-stranded: 1 - 25 mm²
With ferrule: 1 - 16 mm²
Mounting Mounting Standard 35 mm symmetrical DIN rail (EN 60715)
Width 2 Modules (36 mm)
Environmental Operating Temperature -25°C to +55°C (Calibrated at +30°C)
Storage Temperature -40°C to +70°C
Standards & Approvals Primary Compliance IEC/EN 60898-1
Certifications CE, CCC, KEMA, etc.
The ABB S262-C16 is a high-performance, two-pole miniature circuit breaker (MCB) from ABB's System Pro M compact® S200 series. It is a 2-pole (2P) device with a "C" characteristic trip curve and a 16 Ampere rated current per pole. This MCB is engineered for simultaneous overcurrent and short-circuit protection of two independent phase conductors or for providing complete isolation and protection in a single-phase circuit (phase and neutral) where both poles must be switched.