Parameter Category Specification
Series / Frame ABB SACE Emax, E1 Frame (E1.2)
Rated Operational Current (In) 1000 A (Frame rating). Trip setting (Ir) adjustable down to ~400A (per R400 code interpretation).
Rated Operational Voltage (Ue) 690 V AC
Rated Insulation Voltage (Ui) 1000 V AC
Poles 3
Breaking Capacity (Icu at 400V AC) 65 kA (N version)
Mounting Draw-out (Withdrawable) on a truck.
Trip Unit PR121/P Electronic Trip Unit
Protection Functions LI (Long-time & Instantaneous only)
• L (Ir): Adjustable, likely range 0.4 - 1.0 x In (400A - 1000A). The R400 may set a base.
• I (Ii): Adjustable (e.g., 2 - 14 x In) or OFF.
• NO Short-time (S) Delay.
Standard Included Accessories • Draw-out Truck (W) with safety interlocks.
• Handle/Door Coupling Kit (H).
• Shunt Trip (MX) (R) for remote opening.
Typical Additional (Optional) Accessories • Electric Charging Motor (M) - NOT in code. Must verify if included.
• Auxiliary Contacts (OF/SD) - NOT in code. Must verify.
• Undervoltage Release (MN) - NOT in code. Must verify.
Control Voltage Shunt Trip (R) requires an external control supply (e.g., 110V DC, 220V DC, 230V AC). Must be specified separately.
Operation Spring-operated stored energy mechanism. Closing can be manual or electrical (requires separate closing release - XF). Charging is likely manual unless Motor (M) is specified.
Communication The PR121/P trip unit supports communication via an optional add-on module (Ekip Com) for Modbus, Profibus, etc.
Standards IEC 60947-2, UL 489
Typical Application Feeder protection for large loads or sub-distribution where instantaneous tripping is acceptable and selective coordination is provided upstream or is not critical.
The ABB E1N1000 R400 PR121/P-LI WHR 3P is a completely specified, draw-out, low-voltage air circuit breaker (ACB) from the ABB SACE Emax series. This detailed order code defines a 1000A breaker with an advanced electronic trip unit and a comprehensive set of accessories for remote control and status indication.