Parameter Category Specification
Assembly Type High-Current LV Switchgear Functional Unit / Incomer Compartment
Standard IEC 61439-1 & -2
Internal Separation Special High-Current Form (likely F5S). Expect maximum segregation, with separate compartments for busbars, breaker, and cable terminals for safety and maintenance.
Busbar System • Rated Current (Ibm): 4000 A
• Short-Time Withstand (Icw): Very high, typically 80 kA to 120 kA for 1s or 3s.
• Peak Withstand (Ipk): ~2.2 x Icw (e.g., 176 kA to 264 kA).
Main Protective Device • Type: ABB SACE Emax E4 (or large E3) Frame, Draw-out Air Circuit Breaker.
• Likely Rated Current (In): 3200A, 4000A, or 5000A (matching the busbar or slightly lower).
• Poles: 3
• Trip Unit: Advanced Electronic (e.g., PR122/P or PR123/P) for comprehensive protection and metering.
• Breaking Capacity (Icu): Very high, matching the busbar system (e.g., 100 kA, 150 kA at 400V AC).
Key Breaker Features • Heavy-Duty Draw-out Truck (W) with advanced interlocks.
• High-Torque Electric Charging Motor (M).
• Shunt Trip (MX) (P).
Typical Additional Breaker Accessories • Full set of Auxiliary Contacts (OF/SD).
• Undervoltage Release (MN).
• Additional alarm and interlock contacts.
• Communication module for integration into monitoring systems.
Control Voltage Dedicated auxiliary supply for motor and releases (e.g., 220V DC or 230V AC).
Physical Configuration Likely a wide, multi-module compartment. Includes:
• Massive busbar system.
• Heavy-duty draw-out breaker truck with roller mechanism.
• Large cable connection chambers (front/rear).
• Robust shutters and arc containment features.
IP Rating (Enclosure) Typically IP31 or IP41 for indoor switchrooms.
The ABB F5S4000 PR1 3P WMP designates a high-current, low-voltage switchgear functional unit designed for main distribution or large feeder applications. This code specifies an assembly with an extremely robust 4000A busbar system, housing a draw-out, 3-pole air circuit breaker with electronic control and key accessories.