Parameter Category Specification
Series / Frame ABB SACE Emax, E3 Frame
Rated Operational Current (In) 2500 A
Rated Operational Voltage (Ue) 690 V AC
Rated Insulation Voltage (Ui) 1000 V AC
Poles 3
Breaking Capacity (Icu at 400V AC) 50 kA (H version)
Mounting Draw-out (Withdrawable) on a truck with safety interlocks.
Trip Unit Type Thermal-Magnetic (TMD/LI or similar) - Fixed or minimally adjustable.
• Long-time Protection (L) Fixed inverse-time thermal tripping characteristic. Preset to the breaker's rated current (2500A).
• Short-time Protection (S) Not present. No adjustable short-time delay.
• Instantaneous Protection (I) Fixed magnetic trip threshold. The R25 may indicate a specific setting (e.g., 10 x In = 25kA).
• Ground-Fault Protection (G) Not included.
• Adjustability Very limited or none. Cannot be fine-tuned for selective coordination.
Standard Included Accessories • Draw-out Truck (W)
• Electric Charging Motor (M)
• Shunt Trip (MX) (P)
Typical Additional (Optional) Accessories • Auxiliary Contacts (OF/SD) - Not in code, must be verified.
• Undervoltage Release (MN) - Not in code, must be verified.
• Closing Release (XF) - For electrical closing.
Control Voltage Motor (M) and Shunt Trip (P) require an external control supply (e.g., 110V DC, 220V DC). Must be specified separately.
Operation Spring-operated stored energy mechanism. Closing can be manual or electrical (if XF is installed).
Communication None. Thermal-magnetic trip units do not have communication capabilities.
Standards IEC 60947-2, UL 489
Typical Application Main or feeder breaker where selective coordination is not required or is handled upstream. Often used as a backup protection device or for circuits with simple protection needs.
The ABB E3H2500R25WMP3P is a completely specified, draw-out, low-voltage air circuit breaker (ACB) from the ABB SACE Emax series. This dense order code provides all essential information: frame size, breaking capacity, current rating, key accessories, mounting style, and pole count.