Parameter Category Specification
Series / Frame ABB SACE Emax, E3 Frame
Rated Operational Current (In) 2500 A
Rated Operational Voltage (Ue) 690 V AC
Rated Insulation Voltage (Ui) 1000 V AC
Poles 3
Breaking Capacity (Icu at 400V AC) 65 kA (N version)
Mounting Draw-out (Withdrawable) on a truck.
Trip Unit PR11 Electronic Trip Unit
Protection Functions LI (Long-time & Instantaneous only)
• L (Ir): 0.4 - 1.0 x In (1000A - 2500A) adjustable.
• I (Ii): Fixed or adjustable high setting (e.g., 10 x In = 25kA).
• NO Short-time (S) Delay.
Standard Included Accessories • Draw-out Mechanism (W) with safety interlocks.
• Electric Charging Motor (M).
• Shunt Trip (MX) (P) for remote opening.
Typical Additional (Optional) Accessories • Auxiliary Contacts (OF/SD) for status signaling (often included but not in code; verify).
• Undervoltage Release (MN).
• Additional alarm contacts.
Operation Spring-operated stored energy mechanism. Closing can be manual or electrical (requires separate closing release - XF).
Communication The PR11 trip unit typically has limited or no communication capability. For communication, a higher-level trip unit (PR121, PR122) is required.
Standards IEC 60947-2, UL 489
Typical Application Main incoming breaker for large transformers (2000-2500kVA), bus-tie breaker, or feeder for very large loads where selective coordination is achieved upstream or is not required
The ABB SACE E3N 2500 PR11/LI 3P WMP is a high-current, draw-out, low-voltage air circuit breaker (ACB) from the ABB Emax series. This comprehensive order code defines a breaker from the large E3 frame, equipped with a basic electronic trip unit for overload and instantaneous protection, and includes key accessories for remote operation and status indication.