Technical Parameters
Parameter Category Specification
Product Family / Type Self-Powered Three-Phase Voltage Monitoring Relay
Key Monitoring Functions • Correct Phase Sequence (Phase Rotation)
• Phase Loss (Undervoltage per Phase)
• Voltage Asymmetry (Unbalance)
Standard Compliance IEC/EN 60947-5-1
Power Supply Self-powered from the monitored three-phase voltage system. No external auxiliary supply required.
Rated Operational Voltage (Ue) 3 x 208...480 V AC, phase-to-phase. (50/60 Hz). The -70 suffix in this context indicates this wide voltage range.
Operating Voltage Range 0.7 to 1.1 x Ue.
Rated Current Input (In) 1 A AC (This is defined by the -600- in the type code and is related to an optional current-based function for voltage dip monitoring during motor start).
Monitoring Parameters & Settings
• Voltage Threshold (U<) Adjustable via rotary switch. Typically sets the minimum voltage level for phase loss detection.
• Asymmetry Setting Adjustable via rotary switch. Sets the permissible voltage unbalance level between phases (e.g., as a percentage).
• Response Time Fixed delay to prevent nuisance tripping from transient events.
• Phase Sequence Fixed for one rotation (e.g., L1-L2-L3). Trips immediately on reversal.
Output Contact
• Type 1 Changeover (CO) contact (SPDT: 1 NO + 1 NC).
• Rated Operational Current (Ie) 6 A at 250 V AC (AC-15).
Binary Input 1 Reset/Start Input (Terminals A1/A2). A control voltage (matching the -70 range: 48-250V DC/AC) must be applied to close the output relay after a fault or upon initial power-up.
Indications 2 LEDs:
- Green (On) : Supply OK, correct sequence, all parameters within limits.
- Red (Trip) : Fault condition detected (Phase Loss, Sequence Error, or Asymmetry).
Connection Screw-clamp terminals for:
- 3 Phase Voltage Inputs (L1, L2, L3, N optional).
- Output Contact (13, 14, 23).
- Reset Input (A1, A2).
- Optional Current Inputs (for PSR30 models with motor start function).
Electrical Durability ≥ 100,000 mechanical operations.
Isolation Reinforced insulation between voltage circuits, output contact, and reset input.
Operating Temperature -25°C to +55°C
Storage Temperature -40°C to +85°C
Mounting Standard 35mm DIN Rail.
Housing Material Self-extinguishing thermoplastic (Polyamide PA 6.6).
Protection Rating IP40 (front), IP20 (terminals).
Dimensions (W x H x D) Approx. 22.5 mm x 100 mm x 112 mm (1 Module width = 22.5mm).
Weight Approx. 0.15 kg.
Certifications CE, cULus, RoHS.
The ABB PSR30-600-70 is a versatile, self-powered monitoring relay from ABB's PSR (Protection, Signaling, and Control) series. It is designed as a compact, multi-function device for monitoring key electrical parameters in three-phase systems, providing protection against conditions that can damage equipment or disrupt processes.