Key Parameters
Parameter Category Specification
Product Type Brake Chopper Module (External Braking Unit)
ABB Series / Model VPSTB570-600-70
Nominal DC Link Voltage 600 V DC
Maximum Continuous Braking Current 70 A
Maximum Peak Braking Current Typically 150-200% of continuous current for short durations (e.g., 140 A). Refer to datasheet for exact values.
Control / Activation Monitors DC bus voltage. Turns ON when voltage exceeds a preset threshold (typically ~760-780V for a 600V system) and turns OFF when it drops below a reset level.
Power Connection Connects in parallel to the drive's DC bus (+ and - terminals).
Resistor Connection Output terminals for connecting an external braking resistor. The resistor must be sized separately based on the application's braking power and duty cycle requirements.
Key Features • Designed for use with ABB ACS880 and compatible multi-drive systems.
• Provides overvoltage protection for the entire DC bus system.
• Compact module for cabinet installation.
• Includes status indicators and fault signals.
Main Protection • Thermal overload protection for the IGBT.
• Short-circuit protection for the braking resistor circuit.
Typical Mounting Cabinet mounting (IP00). Requires integration into a suitable electrical enclosure.
Core Application Safely dissipating regenerative braking energy in variable speed drive systems with frequent stopping, deceleration, or overhauling loads.
The ABB VPSTB570-600-70 is an external, cabinet-mounted Brake Chopper Module (also known as a braking unit or brake IGBT) designed for use with ABB drives, particularly the ACS880 and ACS580 multi-drive (common DC bus) systems.