Parameters
Parameter Specification / Value
Application Standard IEC/EN 61643-11
Protection Class / Type Type 2 (Class C per UL 1449 4th Ed.)
Rated Voltage (Un) 230/400V AC (50/60 Hz)
Maximum Continuous Operating Voltage (Uc) 255V AC (Line to Neutral)
Nominal Discharge Current (In) 8/20 µs 5 kA
Maximum Discharge Current (Imax) 8/20 µs 20 kA
Voltage Protection Level (Up) @ In ≤ 1.5 kV (Line to Neutral)
Response Time < 25 ns
Short-Circuit Withstand Rating According to IEC 61643-11
Backup Fuse Recommendation gG / gL 16 A (typical, refer to local regulations)
Connection / Cross-Section Plug-in terminal / 1.5 - 4 mm² (stranded or solid)
Housing Material Thermoplastic (UL94 V-0)
Protection Degree (IP) IP20 (when installed in appropriate enclosure)
Operating Temperature Range -40 °C to +80 °C
Status Indication Visual (color flag: green/red)
Mounting DIN-rail mountable (35 mm)
Dimensions (H x W x D) Approx. 90 mm x 18 mm x 62 mm (module size)
The ABB PSPCB-CP-2 is a Surge Protective Device (SPD) Module designed for Commercial and Industrial (C&I) Applications. It is a Compact, Plug-in Cartridge that provides Type 2 / Class C protection against transient overvoltages caused by indirect and direct lightning effects, as well as switching surges within electrical installations.