The Schneider Electric Acti 9 iC65 4P 40A 30mA is a 4-pole (3-phase + neutral), 40A, 30mA Residual Current Circuit Breaker with Overcurrent Protection (RCBO). This integrated device combines a high-performance miniature circuit breaker (MCB) and a sensitive earth leakage protector (RCD) into a single compact unit.
Specifications
Parameter Specification
Product Series Acti 9 iC65
Type RCBO (Residual Current operated Circuit-breaker with integral Overcurrent protection)
Configuration 4 Poles (3P+N) – 3 Protected Poles (Phases) + 1 Protected & Switched Neutral (N).
Rated Current (Iₙ) 40 A (for overload and short-circuit protection)
Tripping Characteristic Typically Type C (Standard, 5-10 × Iₙ) – may vary.
Rated Residual Current (IΔₙ) 30 mA
Residual Current Type Type A (Protects against AC sinusoidal and pulsating DC residual currents) – or Type AC depending on exact model.
Rated Voltage (Uₑ) 400 V AC (3-phase + N systems)
Breaking Capacity (I꜀ₙ) 10 kA (IEC/EN 61009-1)
Protection Functions 1. Overload Protection (Thermal)
2. Short-circuit Protection (Magnetic)
3. Earth Leakage Protection (Residual Current)
Neutral Pole Switched & Protected – Disconnects during tripping and has short-circuit protection.
Mounting DIN Rail (35 mm)
Width 72 mm (4-module width)
Terminals Cage-clamp terminals
Status Indication Mechanical ON/OFF handle with trip flag (often indicates fault type: overcurrent or earth leakage).
Test Function Integrated test button to verify RCD functionality.
Standards IEC/EN 61009-1, CE, RoHS, CCC
Ambient Temperature -25°C to +60°C