The Schneider Electric iST 4P 40R is a Type 2 (Class II) Surge Protective Device from the Acti 9 iST series. Designed with a 4-pole (3P+N) configuration and a built-in remote signaling contact ("R" version), it provides protection against transient overvoltages from indirect lightning strikes and switching operations in three-phase electrical systems, with the added capability for remote monitoring.
Specifications
Parameter Specification
Product Series Acti 9 iST
Model iST 4P 40R
Type / Class Type 2 (Class II) – For installation at main distribution or sub-distribution level.
Configuration 4 Poles (3P+N) – Protects all three phases (L1, L2, L3) and the Neutral.
Nominal Discharge Current (Iₙ) 20 kA (8/20 µs wave, per mode). Note: The "40" in the model likely refers to the Iₘₐₓ value.
Max. Discharge Current (Iₘₐₓ) 40 kA (8/20 µs wave, per mode)
Voltage Protection Level (Uₚ) ≤ 1.5 kV (at Iₙ, typical for 230/400V systems)
Rated Voltage (U꜀) 275V AC (L-N) / 440V AC (L-L) for 230/400V TN-S/TT systems.
Key Feature "R" Integrated Remote Signaling Contact: A built-in changeover contact (NO/NC) that triggers when the SPD reaches a fault or end-of-life state, enabling connection to a Building Management System (BMS), alarm panel, or indicator light.
Status Indication Visual indicator: Green (OK) / Red (Fault).
Backup Protection Requires an external fuse or circuit breaker (typically 32A-63A gG/gL type as per instructions).
Response Time < 25 ns
Mounting DIN Rail (35 mm)
Width 72 mm (4-module width)
Standards IEC/EN 61643-11, CE, RoHS
Operating Temperature -40°C to +80°C