The Schneider Electric NSX100M N 3P 50A is a 3-pole, 50-ampere, Compact NSX series molded case circuit breaker (MCCB) with a standard thermal-magnetic (TM) trip unit. It is a core component of the Compact NSX range, designed for reliable circuit protection, isolation, and control in commercial, industrial, and infrastructure electrical distribution systems. Its compact design offers high performance in a reduced footprint.
Specifications
Parameter Specification
Product Series Compact NSX (formerly known as Compact Masterpact NSX)
Product Line Compact NSX100M
Number of Poles 3-Pole
Rated Operational Current (In) 50 Amperes (This is the fixed rating of the trip unit)
Trip Unit Type N - Standard Thermal-Magnetic (TM-D)
Trip Unit Characteristics • Thermal Protection (Ir): Fixed, matched to the 50A rating.
• Magnetic Protection (Im): Fixed instantaneous trip setting, typically ~10 x In (500A) for standard applications.
Frame Size (Iu max) 100M Frame (Maximum current rating for this physical size is 100A)
Breaking Capacity (Icu @ 400V AC) 50 kA / 70 kA / 100 kA (Selectable based on specific catalog code, e.g., N indicates a standard breaking capacity). The exact value is determined by the suffix in the full part number (e.g., NSX100M N 50A 3P 50 kA).
Rated Operational Voltage (Ue) 690 V AC
Rated Insulation Voltage (Ui) 1000 V AC
Frequency 50/60 Hz
Terminals Standard screw terminals for copper or aluminum cables.
Mounting Fixed or Plug-in versions available. DIN Rail (35mm) or Panel Mount.
Width 105 mm (Typical for a 3-pole version)
Standards IEC/EN 60947-1 & 60947-2, UL 489, CCC, CE, etc.
Electrical Durability 8,000 cycles (minimum)
Mechanical Durability 20,000 cycles (minimum)